Colocation Rack Power Calculator

List the equipment going into your rack to estimate total power, current draw, heat output, and the number of U you need.

DeviceQuantityU per unitWatts per unit
Add:

Default wattages are rough averages and can be edited. Set the voltage to match your facility (230 V in most of Europe, Asia and Africa; 120/208 V in North America). For accurate results, use actual draw from iDRAC/iLO/IPMI or a PDU.

Free, no sign-up. Everything runs in your browser.

How to calculate rack power requirements

  1. Total watts = sum of (watts per unit × number of units).
  2. Amps = watts ÷ (voltage × power factor). At 220 V and PF 0.9, every 1,000 W draws about 5 A; at 120 V it is about 9.3 A.
  3. kVA = watts ÷ power factor ÷ 1,000, used to choose UPS and circuit capacity.
  4. Recommended circuit = amps ÷ 0.8, following the 80% maximum load rule.
  5. Heat = watts × 3.412 BTU/hr.

Colocation planning tips

  • Use dual PSUs and two power feeds (A+B) for production servers, so one circuit can fail without taking equipment down.
  • Measure your servers' actual draw over a few days before you move. PSU label ratings are almost always too high.
  • Leave a few spare U and about 20% power headroom for growth.
  • Note your uplink needs: number of ports, speed (1G/10G), and whether you need public IPs or a BGP session.
FAQ

Frequently asked questions

How do I find out how much power my server uses?

The most accurate way is to measure actual draw through iDRAC, iLO, IPMI, or a metered PDU. The wattage on the power supply (PSU) label is its maximum capacity, not everyday usage; servers typically draw 30–60% of that figure.

What is the difference between watts, amps, and kVA?

Watts are the real power a device consumes. Amps are the electrical current at a given voltage (230 V in most of Europe, Asia and Africa; 120/208 V in North America). kVA is apparent power, watts divided by the power factor, and is used to size UPS units and electrical circuits.

What is the 80% rule for rack circuits?

Common data center practice is to keep continuous load at no more than 80% of the breaker rating. For example, a 16 A circuit should carry at most about 12.8 A, leaving headroom for inrush when equipment powers on so the breaker does not trip.

How many U are in a full rack?

A standard 19-inch data center rack is usually 42U; 45U and 47U racks also exist. One U equals 1.75 inches (44.45 mm) of vertical space. Besides equipment, leave room for patch panels, cable management, and PDUs.

Why calculate heat (BTU/hr)?

Almost all the electrical power a device uses turns into heat. The BTU/hr figure helps estimate cooling requirements; 1 watt produces about 3.412 BTU/hr.